| I. Frame Type | II. Bldg. Height | III. Material Req'd | IV. Use Spec Set |
| Conductive (continuous steel frame) versus non-conductive (wood or masonry frame) | All or part of structure 75' or more above finished grade versus below 75' | Copper or aluminum lightning protection system components | Select proper spec. from this column based on Col. I, II, and III |
These sets are for concrete/masonry or wood frame structures less than 75' tall. The final choice of specification in this group is based on material type. Set 1 uses copper equipment for the entire system. Set 2 makes an aluminum roof system mandatory where this situation is desired or necessary due to roof construction. Copper is still retained for the downlead grounding portions of the system.
| I. Frame Type | II. Bldg. Height | III. Material Req'd | IV. Use Spec Set |
| Non-Conductive | Below | Copper Only | Use Set 1 |
| Non-Conductive | Below | Aluminum on Roof w/Copper Ground | Use Set 2 |