INSTALLATION
  1. EXCAVATE SOIL TO PROVIDE A HOLE ABOUT 12 INCHES IN DIAMETER BY ONE FOOT DEEP. 
  2.  AUGER A 6 TO 7 INCH HOLE, 3 FEET DEEP AT THE CENTER OF THE DEPRESSION. 
  3.  CENTER AND DRIVE THE REQUIRED GROUND ROD UNTIL THE TOP IS APPROXIMATELY THREE INCHES BELOW FINISHED GRADE. 
  4.  SLIDE THE ENHANCEMENT ELECTRODE OVER THE GROUND ROD AS SHOWN WITH THE TOP FLUSH WITH GRADE. MAKE CABLE CONNECTIONS AND RILL THE COPPER PIPE WITH LOW-OHM ENHANCEMENT FILL. 
  5.  MIX ABOUT THREE FOURTHS OF THE EXCAVATED SOIL WITH FIVE POUNDS OF LOW-OHM ENHANCEMENT FILL AND SUFFICIENT WATER TO MAKE A SLURRY. 
  6.  POUR THE SLURRY AROUND THE PIPE GUARDING AGAINST THE FORMATION OF AIR POCKETS. 
  7.  BACKFILL THE REMAINING EXCAVATION WITH THE ORIGINAL SOIL. 
  8.  TRICKLE WATER INTO THE LOW-OHM FILLED TUBE UNTIL IT OVERFLOWS. REPLACE THE INSPECTION CAP AND INSTALLATION IS COMPLETE.
 